ACR405 RECLOSER SERIESDESCRIPTION
Hughes ACR405 series of recloser is designed for use on overhead distribution lines with the voltage range 33-40kV, in distribution substation applications and as an advanced Smart Grid building block.
The ACR405 series model range:
- ACR405 model has the OVX405 vacuum circuit breaker equipped with ABB VG10 2000A/20kA 40.5kV vacuum interrupter, and voltage sensors on the load side;
ACR405 RECLOSER SERIESACR405 MODEL
The ACR405 recloser set includes:
- OVX405 vacuum circuit breaker (compulsory);
- FTU recloser control cabinet (compulsory);
- Interconnecting cable (compulsory);
- External accessories (optional);
The OVX405 vacuum circuit breaker components:
- ABB VG10 2000A/20kA 40.5kV vacuum interrupter (1);
- Integrated 3x phase current transformers (2);
- Integrated voltage sensors on load side (3);
- High current vacuum breaker element (1), RMF type for 1200 A continuous line load and 16 kA fault current in 3 sec;
- Frame (4) made of 5 and 4mm stainless steel to eliminate electrochemical corrosion;
- Electrical circuit (5) made of high grade copper;
- IP67 Control cable contact (6);
- Manual maneuvering (7) of vacuum interrupter;
- Spring stored energy operating mechanism (8);
tHE acr405 RECLOSER additioNAL ACCESSORIES:
- Rugged mounting brackets (1) for different pole types;
- New! Grounding system cable theft alarm (2). See details here;
- Antenna set for GSM/4G including: antenna, multi band professional glass fibre rod; pole mounted bracket for antenna; antenna cable 8M RG-213 N-N professional connectors and surge arresters for antenna N-N connectors;
- Voltage transformer for 33/38kV, phase to phase connected, epoxy insulated with pole mounting brackets;
- Insulations transformator 230/230 VAC
- Surge arresters (3) for 33/38kV with mounting brackets;
- Drop out fuses (4) for 33/38kV with mounting brackets;
Complete list of additional accessories is here.
ACR405 RECLOSERINSTALLATIONS
The ACR405 model of reclosers can be installed on one wooden or concrete pole or between 2 poles.
The standard installation includes below elements in the following sequence:
- Voltage transformer (1)
- Vacuum circuit breaker (2)
- Interconnecting cable (3)
- Recloser control cabinet (4)
ACR405 can installed as one of the blocks of a switchgear scheme.
The installation includes below elements in the following sequence:
- Voltage transformer (1)
- Vacuum circuit breaker (2)
- Recloser control cabinet (3)
ACR405 RECLOSERTECHNICAL DATA
Description | OVX405 |
Rated operation voltage, VDC | 24-48-110 |
Rated maximum voltage, kV | 40 |
Rated basic impulse level, P>P, kV | 185 |
Rated basic impulse level, P>E, kV | 170 |
Power frequency withstand 50/60Hz, Dry, kV | 70 |
Power frequency withstand, Wet, kV | 60 |
Rated power, W | 40 |
Rated continuous current, A | 1200 |
Rated fault making current, kA | 42 |
Rated fault breaking current, kA | 16 |
Rated fault duration time, s | 3 |
Line charging current, A | 5 |
Cable charging current, A | 40 |
Contact resistance, VCB, µΩ | < 40 |
Network frequency, Hz | 50/60 |
Description | Winding 1 |
Phase CT type 1 | 600/1 |
Design min mechanical/electrical | 15.000 |
Dimensions (LxWxH), mm | 1410x621x1070 |
Mass (weight), kg (lbs) | 155 (342) |
Operating temperature C | -45 - +70 |
Humidity | 100% at 25 C |
Enclosure | IP55-65, non-magnetic stainless steel, optional painted in RAL or ANSI colour |
Bushing type | Hydrophobic Cycloaliphatic Epoxy (HCEP) |
Phase to phase distance, mm | 550 |
Creep distance to ground (interrupter isolator), mm | 1310 |
Max installation altitude at rated BIL, m | 3000 |
Description | |
Design specification | IEC 62271-100 |
Marking specification | IEEE std C37.60 |
Operation sequence, no charge | 25 ms trip - 50 ms close - 25 ms trip |
New Auto recloser Application
Hughes Protection Relay App is an unique tool for a modern Electrical Utility Linesman. Operation of the breaker, change of relay parameters etc.