ACR240 RECLOSER SERIESDESCRIPTION
Hughes ACR240 series of recloser is designed for use on overhead distribution lines with the voltage range 22-27kV, in distribution substation applications and as an advanced Smart Grid building block.
The ACR240 series model range:
- ACR240 model has the OVX240 vacuum circuit breaker equipped with 24kV bushings, built-in disconnector and voltage sensors on the load side;
- ACR241 model has the OVX241 vacuum circuit breaker equipped with 27kV bushings and with 1 or 2 sets of voltage sensors on feed and/or load side;
ACR240 RECLOSER SERIESACR240 MODEL
The ACR240 recloser set includes:
- OVX240 vacuum circuit breaker (compulsory);
- FTU recloser control cabinet (compulsory);
- Interconnecting cable (compulsory);
- Built in components (optional);
- External accessories (optional);
The OVX240 vacuum circuit breaker components:
- 24kV bushings (1) of epoxy with silicone surface;
- Integrated and synchronized disconnector (2) with visible open points on all 3-phases;
- Integrated 3x phase current transformers (3) with built-in voltage sensors on load side;
- High current vacuum breaker element (1), AMF type for 630 or 1250A continuous line load and 20kA fault current in 3 sec
- Attachment points (6) for down pole mounted disconnector operation handle;
- Frame (7) made of 5 and 4mm stainless steel to eliminate electrochemical corrosion;
- Electrical circuit (8) made of high grade copper;
- Manual maneuvering of both vacuum interrupter and disconnector;
Optional components:
- Integrated 1x core balance CT for detecting low earth faults;
ACR240 RECLOSER SERIESACR241 MODEL
The ACR241 recloser set includes:
- OVX241 vacuum circuit breaker (compulsory);
- FTU recloser control cabinet (compulsory);
- Interconnecting cable (compulsory);
- Built in components (optional);
- External accessories (optional);
The OVX241 vacuum circuit breaker components:
- Extra insulation with 27kV bushings (1) of epoxy with silicone surfacewith built-in voltage sensors on feed side;
- Integrated 3x phase current transformers (2);
- High current vacuum breaker element (4), AMF type for 630 or 1250A continuous line load and 20kA fault current in 3 sec
- Frame (5) made of 5 and 4mm stainless steel to eliminate electrochemical corrosion;
- Electrical circuit (6) made of high grade copper;
- Manual maneuvering of vacuum interrupter;
Optional components:
- Integrated 1x core balance CT (3) for detecting low earth faults (optional);
- Voltage sensors on load side;
ACR240 RECLOSER SERIESADDITIONAL ACCESSORIES
the acr240/241 RECLOSER EXTERNAL ACCESSORIES:
- Rugged mounting brackets (1) for different pole types;
- New! Grounding system cable theft alarm (2). See details here;
- Antenna set for GSM/4G including: antenna, multi band professional glass fibre rod; pole mounted bracket for antenna; antenna cable 8M RG-213 N-N professional connectors and surge arresters for antenna N-N connectors;
- Voltage transformer for 22/27kV, phase to phase connected, epoxy insulated with pole mounting brackets;
- Insulations transformator 230/230 VAC
- Surge arresters (3) for 22/27kV with mounting brackets;
- Drop out fuses (4) for 22/27kV with mounting brackets;
Complete list of additional accessories is here.
ACR240 RECLOSER SERIESINSTALLATIONS
The ACR240/241 models of reclosers can be installed on one wooden, concrete pole or steel structures.
The standard installation includes below elements in the following sequence:
- Voltage transformer (1)
- Vacuum circuit breaker (2)
- Interconnecting cable (3)
- Recloser control cabinet (4)
ACR240 RECLOSER SERIESTECHNICAL DATA
Description | ovx240 | ovx241 | |
Rated operation voltage, VDC | 24-48-110 | 24-48-110 | |
Rated maximum voltage, kV | 24 | 27 | |
Rated basic impulse level, P>P, kV | 145 | 145 | |
Rated basic impulse level, P>E, kV | 125 | 125 | |
Power frequency withstand, Dry, kV | 60 | 60 | |
Power frequency withstand, Wet, kV | 50 | 50 | |
Rated power, W | 40 | 40 | |
Rated continuous current, A | 630 | 1250 | |
Rated fault making current, kA | 50 | 50 | |
Rated fault breaking current, kA | 20 | 20 | |
Cable charging current, A | 20 | 40 | |
Line charging current, A | 5 | 10 | |
Rated fault duration time, s | 3 | 3 | |
Contact resistance, VCB, µΩ | < 35 | < 35 | |
Contact resistance, ABI, µΩ | < 60 | NA | |
Network frequency, Hz | 50/60 | 50/60 | |
Description | Winding 1 | Winding 2 | Winding 3 |
Phase CT type 1 | 200/1 | 400/1 | 600/1 |
Core balance CT | 20/1 | ||
Description | |||
Design min mechanical/electrical | 20.000 | 20.000 | |
Dimensions (LxWxH), mm | 882x772x957 | 872x370x900 | |
Mass (weight) without air break switch - kg (lbs) | 101 (222) | 101 (222) | |
Mass (weight) with air break switch - kg (lbs) | 125 (275) | NA | |
Description | |||
Operating temperature C | -45 - +70 | -45 - +70 | |
Humidity | 100% at 25 C | 100% at 25 C | |
Eclosure | IP55-65, non-magnetic stainless steel, optional painted in RAL or ANSI colour | ||
Bushing type | Epoxy core with silicone surface | ||
Phase to phase distance, mm | 280 | 280 | |
Creep distance to ground (disconnector isolator), mm | 725 | NA | |
Creep distance to ground (interrupter isolator), mm | 960 | 1090 | |
Max installation altitude at rated BIL, mm | 3000 | 3000 | |
Description | |||
Design specification | IEC 62271-100 | ||
Marking specification | IEEE std C37.60 | ||
Operation sequence, no charge | 25 ms trip - 50 ms close - 25 ms trip |