TVS120 FOR LBSDESCRIPTION
Hughes TVS120 series of sectionalizer is designed for use on overhead distribution lines with the voltage range 6-12kV as an advanced Smart Grid building block.
The tvs120 series for a load break switch model range:
- TVS120 model has the LBS120 vacuum load break switch equipped with 12kV bushings and a built-in disconnector;
- TVS121 model has the LBS121 vacuum load break switch equipped with extra insulated 27kV bushings and optional voltage sensors on feed side;
TVS120 FOR LBSTVS120 MODEL
The tvs120 SECTIONALIZER set for a load break switch includes:
- LBS120 vacuum load break switch (optional);
- TVS150 control cabinet (compulsory);
- Interconnecting cable (optional);
- Built in components (optional);
- External accessories (optional);
The LBS120 vacuum load break switch components:
- 12kV bushings (1) of epoxy with silicone surface;
- Integrated and synchronized disconnector (2) with visible open points on all 3-phases;
- Attachment points (3) for down pole mounted disconnector operation handle;
- Frame (4) made of 5 and 4mm stainless steel to eliminate corrosion;
- Electrical circuit (5) made of high grade copper;
- Manual maneuvering (6) of vacuum interrupter;
- Spring stored energy operating mechanism (7);
Optional components:
- Voltage sensors on load side;
TVS120 FOR LBSTVS121 MODEL
The tvs121 SECTIONALIZER set for a load break switch includes:
- LBS121 vacuum load break switch (optional);
- TVS150 control cabinet (compulsory);
- Interconnecting cable (optional);
- Built in components (optional);
- External accessories (optional);
The LBS121 vacuum load break switch components:
- 27kV bushings (1) of epoxy with silicone surface;
- Attachment points for down pole mounted disconnector operation handle;
- Frame (2) made of 5 and 4mm stainless steel to eliminate corrosion;
- Electrical circuit (3) made of high grade copper;
- Manual maneuvering (4) of vacuum interrupter;
- Spring stored energy operating mechanism (5);
Optional components:
- 1 set of voltage sensors (6) on feed side;
TVS120/121 FOR LBSADDITIONAL ACCESSORIES
TVS120/121 SECTIONALIZER FOR LOAD BREAK SWITCH ADDITIONAL ACCESSORIES:
- Rugged mounting brackets (1) for different pole types;
- New! Grounding system cable theft alarm (2). See details here;
- Antenna set for GSM/4G including: antenna, multi band professional glass fibre rod; pole mounted bracket for antenna; antenna cable 8M RG-213 N-N professional connectors and surge arresters for antenna N-N connectors;
- Voltage transformer for 6/12kV, phase to phase connected, epoxy insulated with pole mounting brackets;
- Insulation transformator 230/230 VAC
- Surge arresters (3) for 6/15kV with mounting brackets;
- Drop out fuses (4) for 6/15kV with mounting brackets;
Complete list of additional accessories is here.
TVS120/121 FOR LBSINSTALLATIONS
The TVS120/121 models of sectionalizers for load break switches can be installed on one wooden or concrete pole.
The standard installation includes below elements in the following sequence:
- Voltage transformer (1)
- Vacuum load break switch (2)
- Interconnecting cable (3)
- Control cabinet (4)
TVS120 FOR LBSTECHNICAL DATA
Description | LBS120 | LBS121 | |
Rated operation voltage, VDC | 24-48-110 | 24-48-110 | |
Rated maximum voltage, kV | 12 | 15 | |
Rated basic impulse level, P>P, kV | 85 | 85 | |
Rated basic impulse level, P>E, kV | 75 | 75 | |
Power frequency withstand, Dry, kV | 60 | 60 | |
Power frequency withstand, Wet, kV | 45 | 45 | |
Rated power, W | 40 | 40 | |
Rated continuous current, A | 630 | 1250 | |
Rated fault making current, kA | 50 | 50 | |
Rated fault breaking current, kA | 20 | 20 | |
Cable charging current, A | 20 | 40 | |
Line charging current, A | 5 | 10 | |
Rated fault duration time, s | 3 | 3 | |
Contact resistance, VCB, µΩ | < 35 | < 35 | |
Contact resistance, ABI, µΩ | < 60 | NA | |
Network frequency, Hz | 50/60 | 50/60 | |
Description | |||
Design min mechanical/electrical | 20.000 | 20.000 | |
Dimensions (LxWxH), mm | 882x745x775 | 872x370x775 | |
Mass (weight) without air break switch - kg (lbs) | 75 (165) | 75 (165) | |
Mass (weight) with air break switch - kg (lbs) | 98 (216) | NA | |
Description | |||
Operating temperature C | -45 - +70 | -45 - +70 | |
Humidity | 100% at 25 C | 100% at 25 C | |
Enclosure | IP55-65, non-magnetic stainless steel, optional painted in RAL or ANSI colour | ||
Bushing type | Epoxy core with silicone surface | ||
Phase to phase distance, mm | 280 | 280 | |
Creep distance to ground (disconnector isolator), mm | 400 | NA | |
Creep distance to ground (interrupter isolator), mm | 650 | 650 | |
Max installation altitude at rated BIL, m | 3000 | 3000 | |
Description | |||
Design specification | IEC 62271-100 | ||
Marking specification | IEEE std C37.60 | ||
Operation sequence, no charge | 25 ms trip - 50 ms close - 25 ms trip |