Autoself,
time-voltage
sectionalizers

Autoself(TM) Time Voltage Sectionalizer TVS is built of the OVX’s high performance outdoor vacuum circuit breaker module and high speed TVX electronic sectionalizer module. The AutoSelf functionality is built on a auto-reclosing cycle count, lockout function and simple time‐voltage logic including multiple timers. It can be operated manually via push buttons and a rotate switch.

Hughes Power System Time Voltage Sectionalizer
  • Non-enclosed switch for extra safety
  • Integrated air break switch for personal safety
  • Operation On and Off with full load without electric power
  • Follows the feeding substations reclosing sequence
  • Easy installation
  • Frame of stainless steel

TVS 120 12kVELECTRICAL DIAGRAM

HUGHES POWER SYSTEM time voltage sectionalizer 12kV

TVS 120 12kVTECHNICAL DATA

Description TVS120 TVS120
Rated maximum voltage 12 kV 15 kV
Rated basic impulse level, P>P 85 kV 85 kV
Rated basic impulse level, P>E 75 kV 75 kV
Power frequency withstand, Dry 60 kV 60 kV
Power frequency withstand, Wet 45 kV 45 kV
Description 12 KV 12 kV
Rated continuous current 630 A 1250 A
Rated fault making current 50 kA 50 kA
Rated fault breaking current 20 kA 25 kA
Cable charging current 20 A 40 A
Line charging current 5 A 10 A
Rated fault duration time 3 s 3 s
Contact resistance, VCB < 35 µΩ < 35 µΩ
Contact resistance,ABI < 60 µΩ < 60 µΩ
Network frequency 50/60 Hz 50/60 Hz
Description    
Design min mechanical/electrical 20.000 20.000
Mass (weight) without air break switch - kg (lbs) 75 (165) 75 (165)
Mass (weight) with air break switch - kg (lbs) 98 (216) 98 (216)
Description    
Ambient temperature C (F) -45 - +70 -45 - +70
Humidity 100% at 25 C 100% at 25 C
Bushing type Epoxy core with silicone surface
Creep distance to group (airbreak switch isolator) 400 mm 400 mm
Creep distance to group (interruptor isolator) 650 mm 650 mm
Max installation altitude at rated BIL 3000 M 3000 M
Description    
Rated operation voltage 220 VAC 110 VDC
Rated power 40 W 40 W
Design specification IEC 62271-100
Marking specification IEEE std C37.60
Operation sequence, no charge 25 ms trip - 50 ms close - 25 ms trip

How can we help?

Thank you for contacting us. Your message has been sent. Our representative will reply to you as soon as posible.

If you are an existing customer and have an urgent need for technical support, please contact your local customer services manager. If you are not sure who that is, please use contact details. You can send a message to us directly by using the form below.

Auto reclosers
  • Auto reclosers
  • Autoself, time-voltage sectionalizers
  • Recloser controls
  • Сontrol cabinets for vacuum breaker modules
  • Kiosk auto reclosers
  • Substations vacuum circuit breaker modules
  • Overhead line vacuum circuit breaker modules
  • Motor operators for airbreak switches
  • Voltage transformers