VXR240 KIOSK RECLOSERDESCRIPTION
Hughes VXR240 series of kiosk recloser is designed for use on underground distribution lines with the voltage range 22-24kV, in distribution substation applications and as an advanced Smart Grid building block.
The VXR240 series model range:
- VXR240 model has the VX4-24 vacuum circuit breaker equipped with 24kV bushings;
VXR240 KIOSK RECLOSERVXR240 MODEL
The vxr240 KIOSK recloser set includes:
- VX4-24 vacuum circuit breaker (compulsory);
- FTU recloser control cabinet (compulsory);
- Interconnecting cable (compulsory);
- Built in components (optional);
- External accessories (optional);
The VX4-24 vacuum circuit breaker components:
- 24kV bushings (1) of epoxy, no SF6 gas or oil;
- High current vacuum breaker element (1), AMF type for 630 or 1250A continuous line load and 25kA fault current in 3 sec;
- Frame (2) made of 5 and 4mm stainless steel to eliminate electrochemical corrosion;
- Electrical circuit (3) made of high grade copper;
- Manual or remote maneuvering (4);
- Padlock facility (5) for mechanical blocking of operation;
Optional components:
- Integrated 3x phase current transformers (6);
- Clip-on current transformers and a core balance transformer for low earth faults detecting (cable mount);
VXR240 KIOSK RECLOSEREXTERNAL ACCESSORIES
the VXR120/240 kiosk recloser EXTERNAL ACCESSORIES:
- Hand crank operated truck mount (1) with interlock function;
- New! Grounding system cable theft alarm (2). See details here;
- Clip-on current transformer, winding: 150/1;
- Core balance transformer (3), winding: 20/1;
- Voltage transformer (4) 1-phase connection 12 or 24/.110 kV class1, 50 VA;
Complete list of external accessories is here.
VXR240 KIOSK RECLOSERINSTALLATIONS
Installation of protection relays and circuit breaker operating panels in a small pre-manufactured substation.
- 4 protection relays (2, 3, 5, 6) for 4 outgoing lines;
- 2 circuit breaker operating panels (7, 8) for 2 incoming cables;
- 1 operating panel (4) for bus bar interconnection circuit breaker;
VXR installation in a substation breaker bay.
- Left: inner protection door closed. Circuit breaker operation buttons (1) extender is mounted on the door;
- Right: VXR (2) installed in a mounting frame (3). Upper side connected to a disconnector (4) with visual open points. Lower side connected to an outgoing cable (5);
VXR120/240 KIOSK RECLOSERTECHNICAL DATA
Description | vx4-12 | vx4-24 | |
Rated operation voltage, VDC | 24-48-110 | 24-48-110 | |
Rated maximum voltage, kV | 12 | 24 | |
Rated basic impulse level, kV | 95 | 125 | |
Rated power, W | 40 | 40 | |
Rated continuous current, A | 630/1250 | 630/1250 | |
Rated fault making current, kA | 63 | 63 | |
Rated fault breaking current, kA | 25 | 25 | |
Cable charging current, A | 20 | 40 | |
Line charging current, A | 5 | 10 | |
Rated fault duration time, s | 3 | 3 | |
Contact resistance, VCB, µΩ | < 35 | < 35 | |
Network frequency, Hz | 50/60 | 50/60 | |
Description | Winding 1 | Winding 2 | Winding 3 |
Phase CT clip-on type | 150/1 | ||
Phase CT type 1 | 200/1 | 400/1 | 600/1 |
Core balance CT | 20/1 | ||
Description | |||
Design min mechanical/electrical | 20.000 | 20.000 | |
Dimensions (LxWxH), mm | 460X447X537 | 587x829x643 | |
Weight, kg | 75 | 95 | |
Description | |||
Operating temperature, °C | -45 - +70 | -45 - +70 | |
Humidity | 100% at 25 C | 100% at 25 C | |
Enclosure | IP55-65, non-magnetic stainless steel, optional painted in RAL or ANSI colour | ||
Bushing type | Epoxy core | ||
Phase to phase distance, mm | 150 | 210 | |
Max installation altitude at rated BIL, m | 3000 | 3000 | |
Description | |||
Design specification | IEC 62271-100 | ||
Marking specification | IEEE std C37.60 | ||
Operation sequence, no charge | 25 ms trip - 50 ms close - 25 ms trip |