High voltage vacuum
circuit breaker

The OVX1100 and OVX720 series of high voltage vacuum circuit breakers are specially designed solid insulated vacuum circuit breakers modularized in 1-2-3 pole configurations. For railway feeder stations it comes with 1 & 2 poles construction, and with 3 poles for electrical transmission system. The product has extremely high mechanical endurance and outstanding electrical parameters with solid insulation and with high performance vacuum interrupters. This combination provides highly reliable maintenance free products with low life cycle costs. Gas free product, environmentally friendly.

Hughes Power System high voltage circuit breaker
  • Solid insulated bushings
  • High current vacuum interrupters
  • High level of insulation
  • Innovative design
  • Low life cycle cost
  • Easily remotely controlled

HUGHES OVX1100DESCRIPTION

Hughes OVX1100 is the world’s first solid insulated high voltage vacuum circuit breaker for 126kV and 3150A for railway feeder substations and electrical transmission system applications. It is a gas-free and a fully environmentally friendly product. The product is built to remain in operation for more than 30 years without major maintenance due to the highest quality materials used in its construction.

The combination of extremely high mechanical endurance and outstanding electrical parameters with solid insulation and with high performance vacuum interrupters provides highly reliable maintenance free products with low life cycle costs.
 

download catalogue

 

send enquiry

HUGHES OVX1100ADVANTAGES

The OVX1100 has the following key advantages:

  • Low maintenance. Hughes vacuum circuit breakers are built to remain in operation for more than 30 years without major maintenance due to the highest quality materials used in its construction;
  • Solid insulated bushings (1) that exclude risk for SF6 or mix gas leakage and oil leakage;
  • High current vacuum interrupters (2) that will not produce any harmful switching products and are very easy to replace in comparison to gas insulated interrupters;
  • The OVX1100 uses high-level insulated bushings (1) with silicone surface that gives superior BIL rating;
  • The vacuum interrupter has an innovative design because the unit can be modularized between 1, 2 or 3 poles for different applications. Normally 1 and 2 poles versions are used for railway electrification and 3 poles version is used for electrical transmission systems including renewable energy sectors;
  • Low life cycle cost is guaranteed due to the combination of extremely high mechanical endurance and outstanding electrical parameters;
  • The circuit breaker is completely prewired which makes it an easily remote-controlled solution;
  • Both connection terminals can be supplied with hole patterns in accordance with ANSI or IEC standards.

HUGHES OVX1100KEY FEATURES

  • Solid insulated;
  • 126 kV 1/2/3-phase;
  • 3150 A, 31.5 kA;
  • 550 kV BIL;
  • 265kV PF@ 50 Hz over open contact;
  • Stored energy mechanical actuator;
  • Solutions for 1-phase, 2-phase, 3-phase systems;
  • Vacuum interrupter enclosed in a solid insulation with silicone surface;
  • Anti-vandalism poles fitted with polymeric insulators as standard;
Hughes vacuum circuit breaker

HUGHES OVX1100TECHNICAL DATA

Description ovx1101/1102/1103
Type outdoor circuit breaker  
Number of phases 1/2/3
Operation mechanism stored energy
Insulators polymeric
Rated frequency, Hz 50/60
Max altitude, m 2000
Rated voltage, kV 126
Insulating medium of contacts vacuum
Rated current conformed to the transformer capacity, A 3150
Rated power frequency withstand voltage (50 Hz/1 min) to earth/across open contact, kV 230/265
Lightning impulse withstand voltage (1.2/50 μs), earth/across open contacts, kV 550/630
Rated breaking current, kA 31.5
Rated making current, kA 85
Make-time, ms ≤100
Break-time, ms ≤50
Longitudinal horizontal static stress, N ≥1000
Horizontal static stress of cross section, N ≥700
Vertical static stress, N ≥700
Creep distance, mm 3970
Working sequence C-0.3-OC-3min-OC
Coil operating voltage, V DC* 110 or 220
Motor operation voltage, V DC* 110 or 220
Rated power of motor, W 600
Number of closing coils 1 x
Power consumption of close coil, W 440
Number of trip coils 2 x
Power consumption of trip coils, W 400
Number of normally open blocking contacts 12 x
Number of normally closed blocking contacts 12 x
Number of switching operations 10,000
Mechanical buttons for closing/opening located in the operating mechanism Yes
Remote/local control switch(electrical) Yes
Close open buttons with LED indicators in cabinet (electrical) Yes
Size (HxLxW), mm 5360 x 2480 x 690
Weight, kg  
Operation voltage 24 VDC, 110 VDC, 220 VAC
Drive voltage 24 VDC, 110 VDC, 220 VAC

How can we help?

Thank you for contacting us. Your message has been sent. Our representative will reply to you as soon as posible.

If you are an existing customer and have an urgent need for technical support, please contact your local customer services manager. If you are not sure who that is, please use contact details. You can send a message to us directly by using the form below.

High voltage circuit breaker
  • High voltage circuit breaker
  • Motor drives for disconnectors
  • Disconnectors for railways
  • Reclosers
  • Recloser controls
  • Time-voltage sectionalizers
  • Kiosk reclosers
  • Indoor vacuum circuit breaker
  • Outdoor vacuum circuit breaker
  • Vacuum load break switches
  • Сontrol units for vacuum circuit breakers